PLC and Industrial Control Solutions for the OEM

ICM-HDLEAK-01 Specifications

   
   
Product Overview Ordering Information Related Products & Accessories Product Support Information
     
Specifications
  # of Probe Inputs 4
  Probe Input Type Sensitivity Adjust approx. 500 -100K Ohms
  AC Excitation Approx. 1.5KHz
  Power Input 12VDC via High Density I/O Bus Power Cable
  Data Output High Density I/O Bus via High Density I/O Data Ribbon Cable
  Led Status Indicators Yes
  Active High / Low Configurable via Jumpers
  Calibration Via Potentiometer for each Channel
  Dimensions 4" Wide x 5" Length x 1.8" Depth
  Mounting Din Rail Mount
  Isolation Optically Isolated Inputs from High Density I/O Bus